The prerequisite for using this guide requires the use of a Windows PC and Maretron’s N2KAnalyzer program installed. The hardware required for Maretron device configuration is the USB100 or IPG100 Gateway connected to a powered N2K network with a FFM100 installed. Please note the DSM250/410/570 can provide the same configuration options as well, but only if the display is running firmware version 1.5.22 or higher.
*If your gasoline engine has a return fuel line, please reference the setup of the Dual Diesel Engine application and use temperature coefficient 0.095 %/°C.
https://www.maretron.com/wp-content/phpkbv95/article.php?id=699
Step 1
Identify the K-factor value for each sensor to be installed. K-factors are located on the sensors label as shown.
* Each sensor may be different, therefore identify appropriately for each engine.

** Please be attentive to direction of flow stamped on product for proper installation
** Proper installation of fuel flow sensors should include a bypass setup for safety as pictured below
Step 2
Connect your wiring to the appropriate channels as presented below (Port 1-6, Stbd 7-12)


Step 3
Connect your Maretron gateway (USB100 or IPG100) to the NMEA2000 network

Step 4
Open Maretron N2KAnalyzer and identify the Maretron FFM100 unit it’s label and Serial Number


Step 5
Once you have identified the Maretron FFM100, right-click and select Configure Device

Step 6
Under the General tab, match your configuration to the details and sample image below
- Operating Mode: Two Independent Sensors
- Sensors for both Channel # 0 and # 1: 3-phase
- Your K-Factor values appropriately for the Port (Channel # 0) and Stbd (Channel # 1)
- Fluid Type: Fuel (Gasoline)
- Instances for Channel # 0 are all 0, label appropriately for Port Engine
- Instance for Channel # 1 is 1, label appropriately for Stbd Engine
- Temperature Source for both Channel # 0 and # 1: User Defined 129

Step 7
Select option Put Config To Device

Step 8
You will receive a confirmation for applying the new configuration details, select OK

Step 9
After completing your configurations of both the Port and Stbd Engines on the FFM100 module, with the engines running, you will now see real time data in the Flow Rate fields.

Now that setup is complete examine data available from the FFM100 ie. fluid flow input and flow output during engine running operation.
Note:
- Both flow rates should be positive numbers.
- If you notice a negative flow rate: examine installation, specifically the orientation of fluid flow arrow located on the sensor lid.
Symptoms of erroneous fluid flow readings such as negative flow rates, more fuel returning to tank than sourced.
Erratic fluid flow rate values:
Most common issues can range from the following application faults:
- Inadequate filtration causing poor sensor performance
- Sensor damage due to debris clogging or damaging sensor internals.
- Fluid pass through (no readings from sensor engine running)
- Sensor wiring issues
- Sensor installation reversed (wiring or physical)