DCR100
DC
Relay Module
User’s Manual
Revision
1.2
Copyright ©2014 Maretron, LLP All
Rights Reserved
Maretron, LLP
http://www.maretron.com
Maretron Manual
Part #: M003001
Revision History
Revision |
Description |
1.0 |
Original document |
1.1 |
Added cautions about using red Loctite and acetone
cleaners Clarified fuse requirements on installation wiring
diagrams |
1.2 |
Added information about configuring channels as
annunciators Added environmental specifications Added information about hardware timers and counters Added information about annunciator operating mode Updated configuration section to reflect new configurable
parameters |
Table of Contents
2.2 Choosing a Mounting Location
2.4.2 Switched Power Connections
2.5.1.1 Current Sensor Zero
Offset Calibration
2.5.1.3 NMEA 2000® PGN
Enable/Disable
2.5.1.4 Restore Factory Defaults
8 Maretron
(2 Year) Limited Warranty
Table of Figures
Figure
1 – Mounting the DCR100
Figure
2 – NMEA 2000® Connector Face Views
Figure
3 – DCR100 Connection Diagram
Figure
4 – Mounting Surface Template
Table of Appendices
Appendix A – NMEA 2000®
Interfacing............................................................................................. A1
This
page intentionally left blank
Congratulations on your purchase of the Maretron DC
Relay Module. Maretron has designed and
built your DCR100 to the highest standards for years of dependable and accurate
service.
Maretron's DCR100 contains 6 Direct Current (DC) relays,
each capable of switching up to 10 Amps. The DCR100 connects directly to an
NMEA 2000® network, so you can turn on and off the relays from a
Maretron DSM150 or DSM250 display or any device running Maretron’s N2KView®
software. The DCR100 easily handles
resistive DC loads like lights, or inductive DC loads like pumps and motors.
The DCR100 can also be used to switch AC circuits using external relays. An
added benefit of the DCR100 is that it reports the current through each of the
six channels. This allows you to determine if loads are drawing too little
electrical current such as burnt out bulbs, or if the loads are starting to
draw too much electrical current. The DCR100 may also be used to connect
annunciators, such as horns or lights, to an NMEA 2000 network for use with
N2KView® alerts.
The Maretron DCR100 is designed to operate within
the harsh demands of the marine environment.
However, no piece of marine electronic equipment can function properly
unless installed, configured, and maintained in the correct manner. Please read carefully and follow these
instructions for installation, configuration, and usage of the Maretron DCR100
in order to ensure optimal performance.
This manual corresponds to DCR100 firmware revision 1.1.2.3.
The Maretron DCR100 has the following features.
Installing the Maretron DCR100 involves the following five
steps. Please refer to the individual sections for additional details.
1.
Unpack the box (Section 2.1)
2.
Choose a mounting location (Section 2.2)
3.
Mount the DCR100 (Section 2.3)
4.
Connect the DCR100 (Section 2.4)
5.
Configure the DCR100 (Section 2.5)
The DCR100 provides
the ability to turn on or off DC power to a load circuit using 6 independent,
isolated solid state relays. The DCR100 is a solid state relay, not a circuit
protection device. Each channel contains protection against overcurrent, over
temperature, and short circuit. These protections are intended to protect the
DCR100, and not the load or the associated wires. Each power source supplying
power to a device which is controlled by the DCR100 must be individually
protected by a circuit breaker. The circuit breaker must be sized appropriately
for the size of the wire from the circuit breaker to the DCR100 and from the
DCR100 to the load device. In addition, the circuit breaker must be no larger
than 10A.
Each channel of the
DCR100 may be manually switched on or off using any of the following methods:
1)
Maretron’s N2KView® software running
on a personal computer*, or
2) Maretron’s
N2KView® software running on a Maretron MBB100 or MBB200C Black Box
for Vessel Monitoring and Control*, or
3)
Maretron’s N2KView® software running
on a Maretron DSM800, TSM800C, or TSM1330C Vessel Monitoring and Control Touchscreen
Computer,
4) a
Maretron DSM150 or DSM250 NMEA 2000®
Multi-function Color Graphic Display, or
5) an
Android or iOS tablet or phone running N2KView Mobile*
The switches can be
monitored and/or controlled through use of the Breaker/Switch component in the
Electrical Distribution category of the Maretron display products listed above.
In addition, the current through each channel may be monitored through the
Breaker/Switch Current component in the Electrical Distribution category of
Maretron display products.
Since the channels
are solid state relays, if the NMEA 2000 power is removed, all switches will
revert to the open (OFF) state. The state that the switch will be in when the
NMEA 2000 power is restored can be configured to be ON, OFF, or in the last
state the switch was in before power was removed.
Each channel has a
hardware timer, which accumulates the elapsed time that channel is in the ON,
OFF, and ERROR states. Also, each channel has a hardware counter, which
accumulates the number of times that the channel has transitioned info the ON,
OFF, and ERROR states. These hardware timers and counters may be viewed and
reset using a Maretron display product or N2KAnalyzer software. If there is a
valid system time reference on the network, the DCR100 will record the date and
time that the timers or counters were reset.
When unpacking the box containing the Maretron DCR100,
you should find the following items:
1 – DCR100
– DC Relay Module
1 – Parts
Bag containing 4 Stainless Steel Mounting Screws
1 – DCR100
User’s Manual
1 –
Warranty Registration Card
If any of these items are missing or damaged, please
contact Maretron.
Please consider the following
when choosing a mounting location.
Attach the
DCR100 securely to the vessel using the included stainless steel mounting
screws or other fasteners as shown in Figure
1
below.
Do not use threadlocking compounds containing methacrylate ester, such as
Loctite Red (271), as they will cause stress cracking of the plastic enclosure.
Figure 1 – Mounting the DCR100
The DCR100 requires two types of electrical connections: 1)
the NMEA 2000® connection (refer to Section 2.4.1),
and 2) the switched power connections, which are described in Section 2.4.2.
The NMEA 2000®
connector can be found on the side of the enclosure. The NMEA 2000®
connector is a round five pin male connector (see Figure 2).
You connect the DCR100 to an NMEA 2000® network using a Maretron
NMEA 2000® cable (or compatible cable) by connecting the female end
of the cable to the DCR100 (note the key on the male connector and keyway on
the female connector). Be sure the cable is connected securely and that the
collar on the cable connector is tightened firmly. Connect the other end of the
cable (male) to the NMEA 2000® network in the same manner. The DCR100
is designed such that you can plug or unplug it from an NMEA 2000®
network while the power to the network is connected or disconnected. Please
follow recommended practices for installing NMEA 2000® network
products.
Figure 2 – NMEA 2000® Connector Face
Views
The DCR100 switched power
connections are made by connecting to the 12-pin terminal strip on the top of
the unit. First, remove the four screws
at the corners of the unit detaching the splash guard from the unit. On the bottom of the splash guard, you will
find a label detailing the wire connection to pin number assignments, which are
repeated in the table below.
Pin # |
Signal Name |
Connection |
1 |
P1 |
Channel
#1 Power |
2 |
L1 |
Channel
#1 Load |
3 |
P2 |
Channel #2
Power |
4 |
L2 |
Channel #2
Load |
5 |
P3 |
Channel #3
Power |
6 |
L3 |
Channel #3
Load |
7 |
P4 |
Channel #4
Power |
8 |
L4 |
Channel #4
Load |
9 |
P5 |
Channel #5
Power |
10 |
L5 |
Channel #5
Load |
11 |
P6 |
Channel #6
Power |
12 |
L6 |
Channel #6
Load |
|
WARNING ·
Each power connection to the DCR100 must be
individually protected with a fuse or circuit breaker which is sized to match
the wire between the breaker/fuse panel and the DCR100, and between the
DCR100 and the load. This fuse or circuit breaker must be sized to be no
larger than 10A. For example, if you are using all six channels of the DCR100, there
must be 6 circuit breakers and a separate power lead from each circuit breaker
to the Px terminal for each
channel. |
The power “Px”
terminals must always be connected to the circuit-breaker protected power
source (which can be wither 12VDC or 24VDC), and the load “Lx” terminals must always be connected to
the power terminal on the load. The other terminal of the load must be
connected to vessel ground. This figure shows the connection of a power and
load connections to the DCR100.
Figure 3 – DCR100 Connection Diagram
Once the NMEA 2000® connection
and switched load connection(s) to the DCR100 have been completed, check to see
that information is being properly transmitted by observing an appropriate NMEA
2000® display. If you don’t
see channel on/off status, refer to Section 4,
“Troubleshooting”.
The DCR100 will transmit data
over the NMEA 2000 network as it is shipped from the factory; however, it may
require configuration, depending on the type of switch monitored. There are
several configurable items within the DCR100, which are detailed in the
remainder of this section.
You configure the ACM100 using Maretron
N2KAnalyzer® software or a Maretron DSM150/DSM250 display or other
NMEA 2000® display unit that is capable of configuring the ACM100.
Please refer to the Maretron N2KAnalyzer
User’s Manual, DSM150 User’s Manual,
or DSM250 User’s Manual, as
appropriate, for details.
Certain
parameters do not normally need to be set in order for normal operation, but
are included in an advanced configuration section for use in special
situations.
The current sensor readings from each
channel may occasionally drift such that you see small positive or negative
current readings from a channel even though no current is flowing. If this
happens, choose this menu option to calibrate the zero offset for the current
sensors for all six channels of the DCR100. Performing this calibration will
place all channels into the “OFF” state.
NMEA
2000® provides a unique device instance for each switch monitoring
device on a vessel. This value should be programmed in each DCR100 so that each
DCR100 is associated with a unique device instance number. The default instance
number is 0, which is used to indicate the first DCR100 that is hooked to the
network. Subsequent DCR100s connected to the network would be numbered 1, 2,
and so on.
You can configure the two installation
description parameters with any text you wish. Examples include date of
installation, location, etc. NMEA 2000 diagnostic tools such as Maretron
N2KAnalyzer® can display this information.
The DCR100 is capable of
transmitting NMEA 2000® messages (or PGNs) associated with monitored
switch circuits. You may individually enable or disable each of these messages.
You may also change the rate of transmission of each of these messages if
desired.
Selecting this configuration option causes all stored
parameters in the DCR100 to be reset to the values they contained when the unit
was manufactured.
Program this parameter with a text string which identifies
this particular DCR100, to allow you to easily distinguish it from other
DCR100’s on the network.
Program this parameter with the instance of the switch bank
controlled by this DCR100. Each switch bank should be programmed with a unique
number. This number is used by a display device to distinguish the switches
controlled by this DCR100 from switches controlled by other devices on the
network.
Each channel has a
text label you can set to identify the load controlled by that channel (for
example, “EXHAUST FAN” or “NAV LIGHTS”). For each channel, set this to a value
which describes the load being controlled so that you can easily identify it in
display devices.
Each channel can be
operated in one of two modes:
·
Normal: the channel operates as a standard NMEA
2000 switch. It can be controlled via N2KView or a DSM150/DSM250 or other NMEA
2000 display with standard NMEA 2000 commands
·
Alert/Annunciator: the channel operates as an
annunciator, similar to the Maretron ALM100. This allows you to connect a
light, horn, bell, siren, or other warning device to the channel and actuate it
from N2KView or a DSM150/DSM250 display in the case of an alert.
The remaining configurable
parameters differ depending on which operating mode is select for the channel.
These are described in the following subsections.
These items are
configurable only when the channel is set to “Normal” mode.
For safety critical
situations or other situations where you don’t want a switch channel’s state changed,
you can use this parameter to set the switch from an “Unlocked” (normal) state,
in which is the switch responds normally to commands over the NMEA 2000®
network, to a “Locked” state, in which the switch will not change state in
response to any commands until it is put back into the “Unlocked” state.
You might lock a
switch into the OFF state if you are servicing equipment that is powered by
that channel, or you might lock a switch into the ON state if the channel powers
a circuit whose power must remain on.
Since the switch
channels in the DCR100 are solid state relays, the switch channels will open
(OFF state) whenever NMEA 2000® power is removed.
This parameter lets
you define the state of this switch channel when the DCR100 is powered up through
the NMEA 2000® network after it has been powered down. You can chose
“ON”, in which case the switch is closed as soon as power is applied; “OFF”, in
which case the switch remains open after power is applied; or “Previous”, in
which case the switch is set to the state it held before power was removed.
This menu allows you to see the current state of each switch
on the DCR100 (“On”, “Off”, or “Error”). It also allows you to set each switch
to the ON or OFF state. Setting the switch to the Off State will clear an Error
condition.
This will reset the
hardware counters for this channel. If a system time is available on the NMEA
2000® network (e.g., from a GPS), the date/time the counters were
reset will be recorded as well.
This will reset the hardware timers for this channel. If a
system time is available on the NMEA 2000® network (e.g., from a
GPS), the date/time the timers were reset will be recorded as well.
These items are
configurable only when the channel is set to “Alert/Annunciator” mode.
Program this
parameter with an instance for the annunciator. Each annunciator device on the
network must have a unique instance number.
Select this option
to test the operation of the annunciator. Pressing this switch will cause any
connected annunciator to emit light or sound.
|
WARNING The DCR100 DC Relay Module is operated under remote
control. Before servicing any load device connected to the DCR100, you must
first disconnect the wire between the DCR100 load terminal and the load
device. Failure to do so can result in serious bodily harm. |
Regular maintenance is important to ensure continued
proper operation of the Maretron DCR100.
Perform the following tasks periodically:
If you notice unexpected
operation of the Maretron DCR100, follow the troubleshooting procedures in this
section to remedy simple problems. If these steps do not solve your problem,
please contact Maretron Technical Support (refer to Section 6
for contact information).
Symptom |
Troubleshooting
Procedure |
No breaker/switch data visible on NMEA 2000®
network. |
|
A breaker/switch always reads “Error” |
The DCR100 may have shut down the affected channel due to
an overtemperature or overcurrent condition detected on the DCR100 relay
itself.
|
A breaker/switch is “ON”, but the load is not powered. |
|
You can see, but not control, the state of a
breaker/switch |
|
As Maretron is constantly
improving its products, all specifications are subject to change without
notice. Maretron products are designed to be accurate and reliable; however,
they should be used only as aids to navigation and not as a replacement for
traditional navigation aids and techniques.
Specifications
Parameter |
Value |
Comment |
Maximum DC Switching
Current |
10 A |
Maximum Current Per
Channel |
DC Switching Voltage |
<32 VDC |
|
Contact Resistance |
<10 mΩ |
|
Current Sense Accuracy |
±100 mA |
|
Certifications
Parameter |
Comment |
NMEA 2000®
Standard |
Level A |
Maritime Navigation and
Radiocommunication Equipment & Systems |
IEC 61162-3 |
Maritime Navigation
and Radiocommunication Equipment & Systems |
Tested to IEC 60945 |
FCC and CE Mark |
Electromagnetic
Compatibility |
NMEA 2000®
Parameter Group Numbers (PGNs)
Description |
PGN # |
PGN Name |
Default Rate |
Periodic Data PGNs |
127501 |
Binary Switch Bank Status |
1 time / 15 seconds and on switch
change |
Response to Requested PGNs |
126464 |
PGN List (Transmit and Receive) |
N/A |
126996 |
Product Information |
N/A |
|
126998 |
Configuration Information |
N/A |
|
Protocol PGNs |
059392 |
ISO Acknowledge |
N/A |
059904 |
ISO Request |
N/A |
|
060928 |
ISO Address Claim |
N/A |
|
065240 |
ISO Address Command |
N/A |
|
126208 |
NMEA |
N/A |
|
Maretron Proprietary PGNs |
126720 |
Configuration |
N/A |
65284 |
DC Relay Current |
1 time per second |
|
130836 |
Switch Status Counter |
1 time / 15 seconds and on switch
change |
|
130837 |
Switch Status Timer |
1 time / 15 seconds |
Electrical
Parameter |
Value |
Comment |
Operating Voltage |
9 to 32 Volts |
DC Voltage |
Power Consumption |
150 mA |
NMEA 2000®
Interface |
Load Equivalence
Number (LEN) |
3 |
NMEA 2000®
Spec. (1LEN = 50 mA) |
Reverse |
Yes |
Indefinitely |
Load Dump Protection |
Yes |
Energy Rated per SAE
J1113 |
Mechanical
Parameter |
Value |
Comment |
Size |
3.50” x 4.20” x 2.03” (88.9mm x 106.7mm x
51.6mm) |
Including Flanges for
Mounting |
Weight |
13 oz. (368.5 g) |
|
Environmental
Parameter |
Value |
IEC 60945
Classification |
Exposed |
Degree of Protection |
IP64 |
Operating Temperature |
-25°C to 55°C |
Storage Temperature |
-40°C to 70°C |
Relative Humidity |
93%RH @40° per
IEC60945-8.2 |
Vibration |
2-13.2Hz @ ±1mm,
13.2-100Hz @ 7m/s2 per IEC 60945-8.7 |
Solar Radiation |
Ultraviolet B, A,
Visible, and Infrared per IEC 60945-8.10 |
Corrosion (Salt Mist) |
4 times 7days @ 40°C,
95%RH after 2 hour Salt Spray Per IEC 60945-8.12 |
Electromagnetic Emission |
Conducted and Radiated
Emission per IEC 60945-9 |
Electromagnetic
Immunity |
Conducted, Radiated,
Supply, and ESD per IEC 60945-10 |
Safety Precautions |
Dangerous Voltage,
Electromagnetic Radio Frequency per IEC 60945-12 |
If you require technical
support for Maretron products, you can reach us in any of the following ways:
Fax: 1-602-861-1777
E-mail: support@maretron.com
World
Wide Web: http://www.maretron.com
Mail: Maretron, LLP
Attn:
Technical Support
9014
N. 23rd Ave Suite 10
Phoenix,
AZ 85021 USA
Please check the dimensions before using the following
diagram as a template for drilling the mounting holes because the printing
process may have distorted the dimensions.
Figure 4 – Mounting Surface
Template
Maretron
warrants the DCR100 to be free from defects in materials and workmanship for two
(2) years from the date of original purchase. If within the applicable
period any such products shall be proved to Maretron’s satisfaction to fail to
meet the above limited warranty, such products shall be repaired or replaced at
Maretron’s option. Purchaser's exclusive remedy and Maretron’s sole obligation
hereunder, provided product is returned pursuant to the return requirements
below, shall be limited to the repair or replacement, at Maretron’s option, of
any product not meeting the above limited warranty and which is returned to
Maretron; or if Maretron is unable to deliver a replacement that is free from
defects in materials or workmanship, Purchaser’s payment for such product will
be refunded. Maretron assumes no liability whatsoever for expenses of removing
any defective product or part or for installing the repaired product or part or
a replacement therefore or for any loss or damage to equipment in connection
with which Maretron’s products or parts shall be used. With respect to products not manufactured by
Maretron, Maretron’s warranty obligation shall in all respects conform to and
be limited to the warranty actually extended to Maretron by its supplier. The foregoing
warranties shall not apply with respect to products subjected to negligence,
misuse, misapplication, accident, damages by circumstances beyond Maretron’s
control, to improper installation, operation, maintenance, or storage, or
to other than normal use or service.
THE
FOREGOING WARRANTIES ARE EXPRESSLY IN LIEU OF AND EXCLUDES ALL OTHER EXPRESS OR
IMPLIED WARRANTIES, INCLUDING BUT NOT LIMITED TO THE IMPLIED WARRANTIES OF
MERCHANTABILITY AND OF FITNESS FOR A PARTICULAR PURPOSE.
Statements
made by any person, including representatives of Maretron, which are
inconsistent or in conflict with the terms of this Limited Warranty, shall not
be binding upon Maretron unless reduced to writing and approved by an officer
of Maretron.
IN
NO CASE WILL MARETRON BE LIABLE FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES,
DAMAGES FOR LOSS OF USE, LOSS OF ANTICIPATED PROFITS OR SAVINGS, OR ANY OTHER
LOSS INCURRED BECAUSE OF INTERRUPTION OF SERVICE. IN NO EVENT SHALL MARETRON’S
AGGREGATE LIABILITY EXCEED THE PURCHASE PRICE OF THE PRODUCT(S) INVOLVED. MARETRON SHALL NOT BE SUBJECT TO ANY OTHER
OBLIGATIONS OR LIABILITIES, WHETHER ARISING OUT OF BREACH OF CONTRACT OR
WARRANTY, TORT (INCLUDING NEGLIGENCE), OR OTHER THEORIES OF LAW WITH RESPECT TO
PRODUCTS SOLD OR SERVICES RENDERED BY MARETRON, OR ANY UNDERTAKINGS, ACTS OR
OMISSIONS RELATING THERETO.
Maretron
does not warrant that the functions contained in any software programs or
products will meet purchaser’s requirements or that the operation of the
software programs or products will be uninterrupted or error free. Purchaser
assumes responsibility for the selection of the software programs or products
to achieve the intended results, and for the installation, use and results
obtained from said programs or products. No
specifications, samples, descriptions, or illustrations provided Maretron to
Purchaser, whether directly, in trade literature, brochures or other
documentation shall be construed as warranties of any kind, and any failure to
conform with such specifications, samples, descriptions, or illustrations shall
not constitute any breach of Maretron’s limited warranty.
Warranty Return
Procedure:
To
apply for warranty claims, contact Maretron or one of its dealers to describe
the problem and determine the appropriate course of action. If a return is
necessary, place the product in its original packaging together with proof of
purchase and send to an Authorized Maretron Service Location. You are
responsible for all shipping and insurance charges. Maretron will return the
replaced or repaired product with all shipping and handling prepaid except for
requests requiring expedited shipping (i.e. overnight shipments). Failure to
follow this warranty return procedure could result in the product’s warranty
becoming null and void.
Maretron
reserves the right to modify or replace, at its sole discretion, without prior
notification, the warranty listed above.
To obtain a copy of the then current warranty policy, please go to the
following web page:
http://www.maretron.com/company/warranty.php
This
page intentionally left blank
Appendix
A – NMEA 2000® Interfacing
DCR100 NMEA 2000® Periodic
Data Transmitted PGNs
PGN
127501 – Binary Switch Bank Status
The DCR100 uses this PGN to transmit the state of each of
the connected switch inputs
Field
1: Indicator
Bank Instance – This field identifies the particular switch bank to which this
PGN applies. Please refer to Section 2.5.3 for instructions on how to
program the value of this field.
2: Indicator
#1 – This field indicates the state of the solid-state relay between the power
source connected to P1 terminal and the load connected to the L1 terminal of
the DCR100. The state will be one of the following values:
·
“OFF”
– The relay channel is open – no current is supplied to the load.
·
“ON”
– The relay channel is closed – current is supplied to the load.
·
“Error”
– The relay channel is open due to an error condition
·
“Data
Not Available” – The channel is configured as “Disabled”
3: Indicator
#2 – This field indicates the state of the solid-state relay between the power
source connected to P2 terminal and the load connected to the L2 terminal of
the DCR100.
4: Indicator
#3 – This field indicates the state of the solid-state relay between the power
source connected to P3 terminal and the load connected to the L3 terminal of
the DCR100.
5: Indicator
#4 – This field indicates the state of the solid-state relay between the power
source connected to P4 terminal and the load connected to the L4 terminal of
the DCR100.
6: Indicator
#5 – This field indicates the state of the solid-state relay between the power
source connected to P5 terminal and the load connected to the L5 terminal of
the DCR100.
7: Indicator
#6 – This field indicates the state of the solid-state relay between the power
source connected to P6 terminal and the load connected to the L6 terminal of
the DCR100.
PGN
65284 – DC Relay Current
The
DCR100 uses this proprietary PGN to transmit the amount of current flowing
through each of the relay channels
Field
1: Manufacturer
Code – This field contains Maretron’s NMEA 2000® manufacturer code, which is
137.
2: Reserved
(2 bits) – This field is reserved by NMEA; therefore, this field always
contains a value of 0x3 (the DCR100 sets all reserved bits to a logic 1).
3: Industry
Group – This field contains the Marine industry group code, which is 4.
4: Bank
Instance – This field identifies the particular switch bank to which this PGN
applies. Please refer to Section 2.5.1.1 for instructions on how to
program the value of this field.
5: Indicator
Number – This field indicates the number of the channel for which current is
being reported. The value of this field can range from 1 to 6.
6: Relay
Current – This field indicates the current flowing through the relay channel in
units of 0.1A.
7: Reserved
– This field is reserved by Maretron; therefore, this field always contains a
value of 0xFFFF (the DCR100 sets all reserved bits to a logic 1).
PGN
130836 – Switch Status Counter
The
DCR100 uses this proprietary PGN to transmit the number of times the switch has
transitioned into the different states since the counter was last reset
Field
1: Manufacturer
Code – This field contains Maretron’s NMEA 2000® manufacturer code, which is
137.
2: Reserved
(2 bits) – This field is reserved by NMEA; therefore, this field always
contains a value of 0x3 (the DCR100 sets all reserved bits to a logic 1).
3: Industry
Group – This field contains the Marine industry group code, which is 4.
4: Indicator
Bank Instance – This field identifies the particular switch bank to which this
PGN applies. Please refer to Section 2.5.1.1 for instructions on how to
program the value of this field.
5: Indicator
Number – This field indicates the number of the channel for which current is
being reported. The value of this field can range from 1 to 6.
6: Start
Date – This field indicates the date on which the counters for this channel
were last reset.
7: Start
Time – This field indicates the time of day on which the counters for this
channel were last reset.
8: OFF
Counter – This field indicates the number of times that this channel has
transitioned to the OFF state since the counters for this channel were last
reset.
9: ON
Counter – This field indicates the number of times that this channel has
transitioned to the ON state since the counters for this channel were last
reset.
10: ERROR
Counter – This field indicates the number of times that this channel has
transitioned to the ERROR state since the counters for this channel were last
reset.
11: Switch
Status – This field indicates the current status of the channel. The state will
be one of the following values:
·
“OFF”
– The relay channel is open – no current is supplied to the load.
·
“ON”
– The relay channel is closed – current is supplied to the load.
·
“Error”
– The relay channel is open due to an error condition
·
“Data
Not Available” – The channel is configured as “Disabled”
12: Reserved
– This field is reserved by Maretron; therefore, this field always contains a
value of 0x3F (the DCR100 sets all reserved bits to a logic 1).
PGN 130836 – Switch Status Timer
The DCR100 uses this proprietary PGN to transmit the total
elapsed time the switch has been in the different states since the counter was
last reset.
Field
1: Manufacturer
Code – This field contains Maretron’s NMEA 2000® manufacturer code, which is
137.
2: Reserved
(2 bits) – This field is reserved by NMEA; therefore, this field always
contains a value of 0x3 (the DCR100 sets all reserved bits to a logic 1).
3: Industry
Group – This field contains the Marine industry group code, which is 4.
4: Indicator
Bank Instance – This field identifies the particular switch bank to which this
PGN applies. Please refer to Section 2.5.1.1 for instructions on how to
program the value of this field.
5: Indicator
Number – This field indicates the number of the channel for which current is
being reported. The value of this field can range from 1 to 6.
6: Start
Date – This field indicates the date on which the timers for this channel were
last reset.
7: Start
Time – This field indicates the time of day on which the timers for this
channel were last reset.
8: Accumulated
OFF Period – This field indicates the total elapsed time that this channel has been
in the OFF state since the timers for this channel were last reset.
9: Accumulated
ON Period – This field indicates the total elapsed time that this channel has been
in the ON state since the timers for this channel were last reset.
10: Accumulated
ERROR Period – This field indicates the total elapsed time that this channel
has been in the ERROR state since the timers for this channel were last reset
. 11: Switch
Status – This field indicates the current status of the channel. The state will
be one of the following values:
·
“OFF”
– The relay channel is open – no current is supplied to the load.
·
“ON”
– The relay channel is closed – current is supplied to the load.
·
“Error”
– The relay channel is open due to an error condition
·
“Data
Not Available” – The channel is configured as “Disabled”
12: Reserved
– This field is reserved by Maretron; therefore, this field always contains a
value of 0x3F (the DCR100 sets all reserved bits to a logic 1).